Task: | Program |
---|---|
Structure: | Combination |
Mathematical Model: | Linear |
Signal: | Discrete |
Function: | Automatic Control, Protection |
Certification: | RoHS, CCC, ISO: 9001, CE |
Suppliers with verified business licenses
General specifications | ||
---|---|---|
Measurement range | 0.2 ... 15 m | |
Reference target | Kodak white (90%) | |
Light source | laser diode typ. service life 85,000 h at Ta = +25 °C |
|
Light type | modulated visible red light | |
Laser nominal ratings | ||
Note | LASER LIGHT , DO NOT STARE INTO BEAM | |
Wave length | 660 nm | |
Beam divergence | < 1.5 mrad | |
Pulse length | approx. 4 ns | |
Repetition rate | 250 kHz | |
max. pulse energy | < 1.5 nJ | |
Angle deviation | max. ± 2° | |
Measuring method | Pulse Ranging Technology (PRT) | |
Diameter of the light spot | < 15 mm at a distance of 15 m at 20 °C | |
Ambient light limit | 50000 Lux | |
Temperature influence | typ. ≤ 0.25 mm/K | |
Functional safety related parameters | ||
MTTFd | 200 a | |
Mission Time (TM) | 10 a | |
Diagnostic Coverage (DC) | 0 % | |
Indicators/operating means | ||
Operation indicator | LED green | |
Function indicator | 2 LEDs yellow for switching state | |
Teach-In indicator | Teach-In: LED green/yellow equiphase flashing; 2.5 Hz Teach Error:LED green/yellow non equiphase flashing; 8.0 Hz |
|
Control elements | 5-step rotary switch for operating modes selection (threshold setting and operating modes) | |
Control elements | Switch for setting the threshold values | |
Electrical specifications | ||
Operating voltage | 10 ... 30 V DC / when operating in IO-Link mode: 18 ... 30 V | |
Ripple | 10 % within the supply tolerance | |
No-load supply current | ≤ 70 mA / 24 V DC | |
Time delay before availability | 1.5 s | |
Interface | ||
Interface type | IO-Link | |
Protocol | IO-Link V1.0 | |
Cycle time | min. 2.3 ms | |
Mode | COM2 (38.4 kBit/s) | |
Process data width | 16 bit | |
SIO mode support | yes | |
Output | ||
Signal output | Push-pull output, short-circuit protected, reverse polarity protected | |
Switching voltage | max. 30 V DC | |
Switching current | max. 100 mA | |
Measurement output | 1 analog output 4 ... 20 mA, short-circuit/overload protected | |
Switching frequency | 50 Hz | |
Response time | 10 ms | |
Conformity | ||
Product standard | EN 60947-5-2 | |
Laser safety | IEC 60825-1:2007 | |
Measurement accuracy | ||
Absolute accuracy | ± 25 mm | |
Repeat accuracy | < 5 mm | |
Approvals and certificates | ||
Protection class | II, rated voltage ≤ 250 V AC with pollution degree 1-2 according to IEC 60664-1 | |
UL approval | cULus Listed, Class 2 Power Source, Type 1 enclosure | |
CCC approval | CCC approval / marking not required for products rated ≤36 V | |
FDA approval | IEC 60825-1:2007 Complies with 21 CFR 1040.10 and 1040.11 except for deviations pursuant to Laser Notice No. 50, dated June 24, 2007 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) | |
Storage temperature | -30 ... 70 °C (-22 ... 158 °F) | |
Mechanical specifications | ||
Housing width | 25.8 mm | |
Housing height | 88 mm | |
Housing depth | 54.6 mm | |
Degree of protection | IP67 | |
Connection | 4-pin, M12 x 1 connector | |
Material | ||
Housing | Plastic ABS | |
Optical face | PMMA | |
Mass | 90 g |
Suppliers with verified business licenses